Maintenance

The performance and service life of PM battery can be optimized by keeping the following guidelines:
1 . Do not use in totally sealed space. The adequate ventilation equipment should be constructed in that space.
2 . To obtain maximum life, take attention to recharge the battery promptly after discharging. Never be stored in a discharged state.
3 . Ambient operation temperature permits in the range of --15oC to 50oC, but 20oC to 25oC would extend life span.
4 . Fasten the battery connections firmly and use shock absorber to protect it from unusual vibrations and shocks during service.
5 . Supply minimum free air space, the distance between batteries is 5mm to 10mm ( 0.02inch to 0.04inch) in connecting.
6 . Avoid mixed use of batteries with different capacities, ages and makers, because the uneven characteristics could cause damage to the battery or the equipment.
7 . To achieve long service life, it is necessary for insulator, plastics or rubber, between battery and rack where the D.C input exceed 60 volts. Also, maintain the greater resistance than one Megaohm between battery and rock in addition to incorporating some alarm circuit to detect any electric leak.
8 . Replace the battery that has the abnormal performance, the crack and deformation of case, electrolyte leakage.
9 . Recharge the battery that has been over-discharged in very low current for many times as soon as it is over-discharged.